Inspection History: ELECTRIC - FINAL
Permit Number - T06CM03066
Inspection Description - ELECTRIC - FINAL
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
08/30/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* RECEIVED LETTERS FOR USE OF ALUMINUM FEEDERS OK FINAL |
|
08/29/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. MISSING EM LIGHT 2ND FLOOR 2. EM LIGHTING NOT OPERATING PROPERLY 2ND FLOOR 3. HP-5 OVER FUSED 4. EXTERIOR EM LIGHTING NOT OPERATING |
|
08/27/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* DO NOT OCCUPY UNTIL FINAL C OF O 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE -- 314.20 2. GROUND SWITCHES AS PER CODE 404.9 3. CLEAN EXCESS DIRT FROM PANELS 110.12 4. LIGHTING DOES NOT MATCH PLAN AT SINK - MODEL ENERGY 5. FINISH PANEL SCHEDULES AS 408.4 6. PLEASE VERIFY 700.12 FOR EXIT LIGHTING |