Permit: T06CM03066

Parcel: 13405116F


Addresses:

994 S HARRISON RD

Inspection Status: Approved

Inspection History: ELECTRIC - CABLE DROP

Date Description Inspector Results Comments
06/04/2007 ELECTRIC - CABLE DROP Approved IVRS - Inspection :*
06/01/2007 ELECTRIC - CABLE DROP Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. PROVIDE LETTER OF TORQUE
2. INSTALL PROTECTIVE BUSHING ON CONDUIT (PVC) ENDS FOR CONDUCTORS 4 & LARGER PER NEC 352
3. PROVIDE INSTALLATION INSTRUCTIONS FOR SWITCHGEAR
4. DRILL BUILDING STEEL & NUT & BOLT GROUND CLAMP OR CADWELD.
02/14/2007 ELECTRIC - CABLE DROP Partial Approval IVRS - Inspection :*
- OK 4" PVC SECONDARYS TEP X-FORMER TO SES
- OK 2" STUB UP'S INTO SES AREA FROM BLD.