Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
Permit Number - T06CM03066
Inspection Description - ELECTRIC - CABLE DROP
Inspection Status - Approved
Date | Description | Inspector | Results | Comments |
---|---|---|---|---|
06/04/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
06/01/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. PROVIDE LETTER OF TORQUE 2. INSTALL PROTECTIVE BUSHING ON CONDUIT (PVC) ENDS FOR CONDUCTORS 4 & LARGER PER NEC 352 3. PROVIDE INSTALLATION INSTRUCTIONS FOR SWITCHGEAR 4. DRILL BUILDING STEEL & NUT & BOLT GROUND CLAMP OR CADWELD. |
|
02/14/2007 | ELECTRIC - CABLE DROP | Partial Approval | IVRS - Inspection :* - OK 4" PVC SECONDARYS TEP X-FORMER TO SES - OK 2" STUB UP'S INTO SES AREA FROM BLD. |