Inspection History: ELECTRIC - ABOVE CEILING

Permit Number - T06CM03066

Inspection Description - ELECTRIC - ABOVE CEILING

Inspection Status - Approved

Date Description Inspector Results Comments
08/30/2007 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
07/17/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK 2ND FLOOR CEILING
07/13/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
2ND FLOOR
1. INSTALL KNOCK OUT SEALS WHERE NEEDED
2. INSTALL DATA/TELEPHONE IN NEAT & WORKMAN LIKE MANNER NEEDS TO BE SUPPORTED EVERY 6'
DO NOT USE OTHER TRADES WORK FOR SUPPORT
3. SUPPORT/SECURE JUNCTION BOXES & EMT
4. TIE WIRES USED AS SUPPORT TO BE SECURED AT BOTH ENDS
5. INSTALL BLANK COVER ON OPEN JUNCTION BOX
6. BLANK OPEN ENDS OF SPARE EMT'S INTO PANELS
7. ENSURE MC CABLE IS UP OFF OF GRID
8. STRAP MC CABLES WITHIN 12" OF JUNCTION BOXES
9. ENSURE ALL LIGHTING FIXTURES HAVE TIE WIRES.
06/19/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
FIRST FLOOR
1. INSTALL 12 GAUGE SEISMIC WIRE ON ALL EXITS
2. OK TO CLOSE CEILINGS 1ST FLOOR
05/25/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
FIRST FLOOR
1. NEED TO CHECK RECESSED FIXTURES ATTACHED TO GRID NO CEILING TILES ON JOB SITE.
2. NEED TO INSTALL TELEPHONE/DATA CABLES.
3. CANNOT USE SJ CORD FOR PERMANENT WIRING OF BUILDING.
4. INSTALL THERMOSTAT CABLE IN NEAT & WORKMANLIKE MANNER. SUPPORT OFF CEILING GRID EVERY 6'
5. MOVE INSTALLATION AWAY FROM RECESSED FIXTURES
6. CHECK RECESSED FIXTURES LISTED FOR DAMP LOCATION.
7. PLUG SPARE CONDUITS INTO PANELS
8. CHECK ALL CEILING JUNCTION BOXES MADE UP
9. NEED TO INSPECT FIRE ALARM SMOKE DETECTOR 1ST FLOOR LOBBY.