Permit: T06CM03017

Parcel: 110060930

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/22/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
01/29/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
01/09/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE AN OVERFLOW SENSOR ON SECONDARY DRAIN OUTLETS OR PIPE CONSPICUOUS
- FURNACE VENT CANNOT TERMINATE INTO A DIRECT VENT HOOD.
- THIS IS NOT A DIRECT VENT FURNACE
- SCREW WATER HEATER VENT TO DRAFT DIVERTER
- PROVIDE FUSES AND SECURE CONDUITS AND DISCONNECTS
- SEAL AROUND COIL CONNECTION TO FURNACE
- REMOVE ALL FOIL TAPE FROM APPLIANCE VENTS