Permit: T06CM03017

Parcel: 110060930

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
01/15/2008 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
06/27/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/26/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK TO COVER WALLS
ENSURE PROPER ALIGNMENT AT TUB OVERFLOW
CALL FOR CLOSET FLANGE INSP. AFTER FINISHED FLOOR
06/07/2007 PLUMBING - INTERMEDIATE Denied 9999 ACCESS CODE
1. BANG PLATES ON ALL TUBING WITHIN 1 1/4" OF STUD FACE
2. SECURE PEX TUBING
3. WATER HEATER INSTALLED ON WOOD PLATFORM REQUIRES DRAIN PAN.
4. SECURE TUB DIVERTORS.
5. INSTALL CLOSET FLANGES AT CORRECT ELEVATION
SEE UPC IS #5 PG. 320
6. USE BRASS OR STAINLESS SCREWS ON UPPER FLOORS.
7. PLAN SPECIFIES 1" BLK STEEL GAS PIPING
8. PROTECT COPPER FROM STUCCO
9. 18" OF METALLIC TUBING REQUIRED AT WH
10. DWV TEST OK
06/05/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
GATE LOCKED