Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/28/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* OK ROUGH |
|
| 06/25/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* OK ROUGH SUBJECT TO APPROVED STAMP |
|
| 06/06/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. STAPLE CABLES UNDER STAIRS - NOT SHEATHING HANGER 2. TIGHTEN LOOSE FITTING/CONNECTOR OUTSIDE WALL BOXES. 3. WHERE IS CITY OR WILDAN STAMP FOR ELECTRICAL REVISIONS? 4. FINISH ITEM #2 PREVIOUS INSPECTION. |
|
| 05/21/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :$ | |
| 05/21/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. SCREWS NOT ALLOWED IN FRONT PORTION OF BOXES 314.23 2. SUPPORT NM CABLES WITHIN 12" OF CANS & EXHAUST FANS 3. SEPARATE CABLE FROM BUNDLING AND CORRECTLY SUPPORT STUBOUT FOR PANEL. 4. FAN BOXES OVERFILLED 5. LIGHT FIXTURE FOR KITCHEN AND CLOSET DO NOT MATCH PLANS -- PLEASE REVISE PLANS OR INSTALL AS DRAWN. |