Permit: T06CM03017

Parcel: 110060930

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
06/28/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
OK ROUGH
06/25/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK ROUGH SUBJECT TO APPROVED STAMP
06/06/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. STAPLE CABLES UNDER STAIRS - NOT SHEATHING HANGER
2. TIGHTEN LOOSE FITTING/CONNECTOR OUTSIDE WALL BOXES.
3. WHERE IS CITY OR WILDAN STAMP FOR ELECTRICAL REVISIONS?
4. FINISH ITEM #2 PREVIOUS INSPECTION.
05/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :$
05/21/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SCREWS NOT ALLOWED IN FRONT PORTION OF
BOXES 314.23
2. SUPPORT NM CABLES WITHIN 12" OF CANS & EXHAUST FANS
3. SEPARATE CABLE FROM BUNDLING AND CORRECTLY SUPPORT STUBOUT FOR PANEL.
4. FAN BOXES OVERFILLED
5. LIGHT FIXTURE FOR KITCHEN AND CLOSET DO NOT MATCH PLANS -- PLEASE REVISE PLANS OR INSTALL AS DRAWN.