Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/25/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 05/21/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. AT SPRINKLER PIPE BOND -- OUTSIDE A. REMOVE PAINT UNDER CLAMP & SECURE THE BOND WIRE NEC 250.12 2. BOND CLAMP TO SPRINKLER IN CEILING WRONG SIZE NEC 110.3B 3. PANEL DIRECTORYS STILL NOT CORRECT 4. CKT TO DISHWASHER, DISPOSAL, INSTA-HOT UNDERSIZED NEC 422, 220 |
|
| 05/18/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. BOND METAL PIPING SYSTEMS TO SERVICE -- NEC 250.104 2. CHECK EMERGENCY LIGHTING FOR PROPER OPERATION ALSO, TO BE FED BY LIGHTING CKT FOR THAT AREA -- NEC 700.12 3. GROUND #6 & SMALLER TO BE GREEN OR BARE ENTIRE LENGTH -- NEC 350.119 4. PANEL DIRECTORY TO BE CORRECT, LEGIBLE - NEC 408.4 5. FINISH WATER HEATER/DISPOSAL WIRING 6. INSTALL ALL COVER PLATES |
|
| 05/14/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* |