Permit: T06CM03002

Parcel: 108240820


Addresses:

2496 E RIVER RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/25/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
05/21/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. AT SPRINKLER PIPE BOND -- OUTSIDE
A. REMOVE PAINT UNDER CLAMP & SECURE THE BOND
WIRE NEC 250.12
2. BOND CLAMP TO SPRINKLER IN CEILING WRONG SIZE
NEC 110.3B
3. PANEL DIRECTORYS STILL NOT CORRECT
4. CKT TO DISHWASHER, DISPOSAL, INSTA-HOT UNDERSIZED
NEC 422, 220
05/18/2007 ELECTRIC - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. BOND METAL PIPING SYSTEMS TO SERVICE -- NEC 250.104
2. CHECK EMERGENCY LIGHTING FOR PROPER OPERATION
ALSO, TO BE FED BY LIGHTING CKT FOR THAT AREA --
NEC 700.12
3. GROUND #6 & SMALLER TO BE GREEN OR BARE ENTIRE LENGTH -- NEC 350.119
4. PANEL DIRECTORY TO BE CORRECT, LEGIBLE - NEC 408.4
5. FINISH WATER HEATER/DISPOSAL WIRING
6. INSTALL ALL COVER PLATES
05/14/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*