Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/22/2008 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 01/18/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* |
|
| 01/15/2008 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. UFER NEVER INSPECTED, NEED TO DRIVE GROUND RODS ALSO 2. BOND FOR SERVICE RISER UNDERSIZED - NEC 250.66 3. IDENTIFY "SERVICE DISCONNECTS" AS SUCH - NEC 230.72B 4. IDENTIFY UNIT #'S AT SERVICE 5. NEED INHIBITOR ON ALL ALUMINUM TERMINATIONS - NEC 110 6. CONNECT ALL GROUNDS 7. HAVE WRONG SIZE CLAMPS ON GAS PIPE (TOO BIG) NEC 110.3 B 8. EQUIPMENT TO BE OPEN FOR INSPECTION |