Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 06/20/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 06/19/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INTERIOR INSPECTION 1. GROUND ALL METAL BOXES 2. USE A CONNECTOR WHERE ROMEX ENTERS METAL BOX 3. PIGTAIL NEUTRAL AT DISH/DISP J-BOX, IDENTIFY WHITE USED AS HOT FOR SWITCH LEG, WILL NEED TWO POLE BREAKER FOR THIS CKT (DISH/DISP) SINCE TWO HOTS WILL SUPPLY RECEPTACLE. 4. SECURE BOXES IN BLOCK WALL 5. BOND GAS PIPES TO SERVICE 6. INSTALL NAIL PLATES AS NEEDED, WHERE HOLE IS 1 1/4" OR LESS FROM STUD FACE (CHECK HOME RUNS ABOVE PANEL TOO) 7. STAPLE ROMEX (LOOSE) IN WALLS, CEILINGS 8. RECEPTACLES TO BE NO FURTHER THAN 12 FEET APART ALONG WALLS, NO MORE THAN 6' FROM BROKEN WALL LINE. |