Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 12/04/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE BLOCKING FOR PVC CONDENSATE PIPING NOT TO EXCEED 4 FEET - PAINT ALL PVC CONDENSATE PIPING WITH LATEX PAINT THAT IS EXPOSED TO SUNLIGHT - CONDENSING UNITS NOT PROPERLY FUSED - PROVIDE APPROVED COVER AT REMOVE CONDENSING UNIT - SEAL ROOF JACK AT EVAP. COOLER - PROVIDE OUTSIDE AIR PER PLANS - PROVIDE PROPER FLUE PIPE LENGTH ABOVE PARAPET WALL PER 503.5.4 IFGC - PROVIDE BALANCE ON HOOD PER PLANS |