Permit: T06CM02811

Parcel: 11922182F


Addresses:

1777 W 36TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
02/07/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
12/04/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE BLOCKING FOR PVC CONDENSATE PIPING NOT TO EXCEED 4 FEET
- PAINT ALL PVC CONDENSATE PIPING WITH LATEX PAINT THAT IS EXPOSED TO SUNLIGHT
- CONDENSING UNITS NOT PROPERLY FUSED
- PROVIDE APPROVED COVER AT REMOVE CONDENSING UNIT
- SEAL ROOF JACK AT EVAP. COOLER
- PROVIDE OUTSIDE AIR PER PLANS
- PROVIDE PROPER FLUE PIPE LENGTH ABOVE PARAPET WALL PER 503.5.4 IFGC
- PROVIDE BALANCE ON HOOD PER PLANS