Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - HOOD SYSTEMS
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/07/2008 | MECHANICAL - HOOD SYSTEMS | Approved | IVRS - Inspection :* HOOD SYSTEMS APPROVED |
|
| 12/04/2007 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* - PROVIDE BLOCKING FOR PVC CONDENSATE PIPING NOT TO EXCEED 4 FEET - PAINT ALL PVC CONDENSATE PIPING WITH LATEX PAINT THAT IS EXPOSED TO SUNLIGHT - CONDENSING UNITS NOT PROPERLY FUSED - PROVIDE APPROVED COVER AT REMOVE CONDENSING UNIT - SEAL ROOF JACK AT EVAP. COOLER - PROVIDE OUTSIDE AIR PER PLANS - PROVIDE PROPER FLUE PIPE LENGTH ABOVE PARAPET WALL PER 503.5.4 IFGC - PROVIDE BALANCE ON HOOD PER PLANS |
|
| 10/31/2007 | MECHANICAL - HOOD SYSTEMS | Not ready for Inspection | IVRS - Inspection :* ANSUL SYSTEM TO SHUT DOWN MUA & LIGHTS IN HOOD WHILE EXHAUST REMAINS RUNNING |
|
| 10/29/2007 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* PROPER MAKE UP AIR UNIT STILL NOT INSTALLED. PLANS MAY HAVE BEEN APPROVED IN ERROR REFER TO M.U.A |
|
| 11/28/2006 | MECHANICAL - HOOD SYSTEMS | Not ready for Inspection | IVRS - Inspection :* HOOD DUCT HAS BEEN WRAPPED HOWEVER, ELECTRICAL IS NOT COMPLETE FOR HOOD LIGHT. HOOD SIDE TRIM MAY NEED TO BE REMOVABLE DEPENDING ON WIRING METHOD TO LIGHT - DO NOT INSTALL TRIM YET. |
|
| 10/27/2006 | MECHANICAL - HOOD SYSTEMS | Partial Approval | THIS PROBLEM STILL EXISTS EX-DUCT, TYPE I HOOD, OK OK TO WRAP HOOD PROGRESSING |
|
| 10/16/2006 | MECHANICAL - HOOD SYSTEMS | Partial Approval | IVRS - Inspection :* 1. SUGGEST TOTAL COMPENSATING HOOD OR NEED TO HAVE A TEMPERED MAKE UP AIR UNIT, IF INST. AS PER PLAN. CONSULT ARCHITECT FOR DIRECTIONS. NOTE: SUPPLY DUCT SYSTEM - NEED TO WRAP SUPPLY DUCT FITTINGS. |