Permit: T06CM02811

Parcel: 11922182F


Addresses:

1777 W 36TH ST

Inspection Status: Approved

Inspection History: MECHANICAL - HOOD SYSTEMS

Date Description Inspector Results Comments
02/07/2008 MECHANICAL - HOOD SYSTEMS Approved IVRS - Inspection :*
HOOD SYSTEMS APPROVED
12/04/2007 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
- PROVIDE BLOCKING FOR PVC CONDENSATE PIPING NOT TO EXCEED 4 FEET
- PAINT ALL PVC CONDENSATE PIPING WITH LATEX PAINT THAT IS EXPOSED TO SUNLIGHT
- CONDENSING UNITS NOT PROPERLY FUSED
- PROVIDE APPROVED COVER AT REMOVE CONDENSING UNIT
- SEAL ROOF JACK AT EVAP. COOLER
- PROVIDE OUTSIDE AIR PER PLANS
- PROVIDE PROPER FLUE PIPE LENGTH ABOVE PARAPET WALL PER 503.5.4 IFGC
- PROVIDE BALANCE ON HOOD PER PLANS
10/31/2007 MECHANICAL - HOOD SYSTEMS Not ready for Inspection IVRS - Inspection :*
ANSUL SYSTEM TO SHUT DOWN MUA & LIGHTS IN HOOD WHILE EXHAUST REMAINS RUNNING
10/29/2007 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
PROPER MAKE UP AIR UNIT STILL NOT INSTALLED.
PLANS MAY HAVE BEEN APPROVED IN ERROR REFER TO M.U.A
11/28/2006 MECHANICAL - HOOD SYSTEMS Not ready for Inspection IVRS - Inspection :*
HOOD DUCT HAS BEEN WRAPPED HOWEVER, ELECTRICAL IS NOT COMPLETE FOR HOOD LIGHT. HOOD SIDE TRIM MAY NEED TO BE REMOVABLE DEPENDING ON WIRING METHOD TO LIGHT - DO NOT INSTALL TRIM YET.
10/27/2006 MECHANICAL - HOOD SYSTEMS Partial Approval THIS PROBLEM STILL EXISTS
EX-DUCT, TYPE I HOOD, OK
OK TO WRAP
HOOD PROGRESSING
10/16/2006 MECHANICAL - HOOD SYSTEMS Partial Approval IVRS - Inspection :*
1. SUGGEST TOTAL COMPENSATING HOOD OR NEED TO HAVE A TEMPERED MAKE UP AIR UNIT, IF INST. AS PER PLAN. CONSULT ARCHITECT FOR DIRECTIONS.

NOTE: SUPPLY DUCT SYSTEM - NEED TO WRAP SUPPLY DUCT FITTINGS.