Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/29/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 04/18/2007 | MECHANICAL - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* R4.2 FLEX DUCT NOT ACCEPTABLE INSULATE ALL FITTINGS WITH MIN. 2" R5 FOIL WRAP STRAP ALL FLEX EVERY 5' FRP CANNOT BE WITHIN 18" OF THE HOOD TOP OF HOOD MUST BE FIRE BLANKETED IF NOT 18" CLEARANCE |