| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 02/08/2007 | MECHANICAL - INTERMEDIATE | Approved | IVRS - Inspection :* 1) OK FOR SHEETROCK |
|
| 02/06/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) SEE NOTES FROM 2/5/07 |
|
| 02/05/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1) STILL NO BACKING AROUND CEILING BOXES 2) EXHAUST DUCT STILL NOT THRU THE ROOF |
|
| 01/25/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* CORRECTIONS HAVE NOT BEEN MADE |
|
| 01/04/2007 | MECHANICAL - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. DRYER VENT PIPE COMING APART AT THE SEAM NEAR ELBOW. 2. LOWER THE WATER HEATER VENT & PROVIDE AS MUCH SLOPE AS POSSIBLE & STILL MAINTAIN 1" CLEARANCE FROM COMBUSTIBLES. 3. ELBOW MUST BE BELOW CEILING FOR FINAL CONNECTION. 4. 2ND FLOOR EXHAUST DUCT NOT UP THRU ROOF. 5. PROVIDE BACKING AROUND CEILING BOXES. |
|
| 10/12/2006 | MECHANICAL - INTERMEDIATE | Partial Approval | IVRS - Inspection :* APP. PLAN SHOWS B-1 WATER HTR. VENT UP THRU ROOF AS INSTALLED, ITS OFFSETTING THRU GARAGE IF ACCEPTABLE AS INSTALLED, TOTAL VERTICAL WILL NEED TO BE 25% LONGER THAN THE HORIZONTAL. |