Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/06/2007 | ELECTRIC - CABLE DROP | Approved | IVRS - Inspection :* | |
| 04/05/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* COMPLETE INSPECTION ITEMS FROM PREVIOUS INSPECTION ON 4/4/07 |
|
| 04/04/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. INSTALL GROUND CLAMP FOR GAS BOND 2. SEAL OPEN KNOCKOUT BOTTOM OF PANEL 3. GROUND RODS TO BE MIN. 6' APART & MUST BE COMPLETELY DRIVEN |