Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/18/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 11/17/2006 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. RESTROOM STRUCTURE - OK NEED TO LOOK AT 480V TRANSFORMER CONNECTIONS AND TRANSFORMER TIE INTO GEAR. WILL NEED WITH RMS ON REST OF UNDERGROUND WILL NEED REJECT PINS AT DISCONNECT |
|
| 11/17/2006 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* NEED REJECT PINS IN DISCONNECT AFTER TRANSFORMER. |