Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - CABLE DROP
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/20/2010 | ELECTRIC - CABLE DROP | Approved | finaled by aalegria during building inspection 3-7-7 | |
| 01/11/2007 | ELECTRIC - CABLE DROP | Partial Approval | SERVICE OK, STRAP GROUND WIRE TO STRUCTURE, DRIVE GROUND RODS FLUSH TO GRADE OR BELOW. |
|
| 01/02/2007 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. UFER WAS NOT INSPECTED 2. REVISED PLANS SHOW 150A SERVICE TO EACH MIN. 3. INSTALL ADDRESSES |
|
| 12/27/2006 | ELECTRIC - CABLE DROP | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. UFER WAS NOT INSPECTED 2. EACH APT DRAWS 107 AMPS AND PNL SHOW IS 200 AMPS ON PLAN 3. SERVICE MAINS WERE TO BE LARGER THAN 100 A 4. SERVICE NOT ADDRESSED 5. CALL OFFICE 791-5550 AND ASK FOR STEVE LONG TELL HIM YOU NEED TO APPLY FOR AN OVERHEAD WAIVER. |