Permit: T06CM01936

Parcel: 113050580


Addresses:

1925 E GREENLEE RD

Inspection Status: Partial Approval

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
04/10/2006 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. #8 WIRE ACCEPTABLE FOR 50 AMP. MAX.
2. BLOCK/CLAMP, SECURE FLEX HI OOLAGE & CONTROL WIRING CIRC.
3. DOES THIS FAN COIL HAVE 10 KW AUX.
HT. STRIP?
MARK DATA PLATE TO VERIFY ACTUAL SIZE.
THIS NEEDS #6 WIRE, SWITCH INTO FAN COIL.
4. PROVIDE TRAP AT COND. COIL DISCHARGE AHEAD OF PUMP.