Inspection History Details
Inspection Status: Not Applicable
Inspection History: SITE - SEWER
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/23/2007 | SITE - SEWER | Not Applicable | IVRS - Inspection :* | |
| 08/15/2007 | SITE - SEWER | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSTALL A BUSHING ON THIN WALL PIPE TO MAKE OD SAME AS SCH 40 |
|