Permit: T06CM01495

Parcel: 10705146A

Inspection Status: Approved

Inspection History: ELECTRIC - TEMP POWER FOR TEST

Date Description Inspector Results Comments
10/24/2007 ELECTRIC - TEMP POWER FOR TEST Approved IVRS - Inspection :*
10/19/2007 ELECTRIC - TEMP POWER FOR TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. ARRANGE BONDING CONDUCTOR BETWEEN METER BASE AND DISCONNECT TO PREVENT OBJECTIONABLE CURRENT
SEE NEC 250.6
2. INSTALL SECOND DISCONNECT COVER SCREW

NOTE: METER ENCLOSURE MADE HOT BY TEP BEFORE APPROVAL, METER BASE UNSEALED AT TIME OF INSPECTION.