Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - TEMP POWER FOR TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/24/2007 | ELECTRIC - TEMP POWER FOR TEST | Approved | IVRS - Inspection :* | |
| 10/19/2007 | ELECTRIC - TEMP POWER FOR TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999* 1. ARRANGE BONDING CONDUCTOR BETWEEN METER BASE AND DISCONNECT TO PREVENT OBJECTIONABLE CURRENT SEE NEC 250.6 2. INSTALL SECOND DISCONNECT COVER SCREW NOTE: METER ENCLOSURE MADE HOT BY TEP BEFORE APPROVAL, METER BASE UNSEALED AT TIME OF INSPECTION. |