Permit: T06CM01023

Parcel: 110102910

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
11/29/2006 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
11/22/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1) EXIT LIGHTING NOT WORKING
2) PLEASE REUSE LIGHTING SCHEDULE AND ENERGY ?
3) LABEL BREAKER TO AREA
4) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20
5) WAITING ON REVISED DRAWINGS FOR SERVICE
6) OK WATER BOND
11/16/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
11/14/2006 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
NEED REVISED PLANS FOR SERVICE.
10/13/2006 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. CORDS NOT ALLOWED ABOVE CEILNG 400.7 & 8

OK TO TILE EXCEPT AS NOTED.