Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/29/2006 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 11/22/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) EXIT LIGHTING NOT WORKING 2) PLEASE REUSE LIGHTING SCHEDULE AND ENERGY ? 3) LABEL BREAKER TO AREA 4) BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEED APPROVED EXTENDER RINGS 314.20 5) WAITING ON REVISED DRAWINGS FOR SERVICE 6) OK WATER BOND |
|
| 11/16/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* | |
| 11/14/2006 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* NEED REVISED PLANS FOR SERVICE. |
|
| 10/13/2006 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. CORDS NOT ALLOWED ABOVE CEILNG 400.7 & 8 OK TO TILE EXCEPT AS NOTED. |