Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 10/09/2006 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 09/29/2006 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* CONTROL WIRING EXPOSED AT CONDENSOR MUST BE IN CONDUIT OR PROTECTED FROM DAMAGE. PROVIDE A DISCONNECT AT CONDENSOR. |
|
| 09/21/2006 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE A SECONDARY DRAIN TO A CONSPICUOUS LOCATION. - SUPPORT T-STAT WIRE PER N.E.C - FAN COIL NOT FUSED CORRCTLY - PROVIDE A FRESH AIR INTAKE. - HORIZONTAL SECTION OF CONDENSATE REQUIRES MIN. 1/8" PER FT. SLOPE. - PAINT EXPOSED PVC W/LATEX PAINT - PROVIDE A DISCONNECT FOR CONDENSOR. |