Permit: T06CM00914

Parcel: 14103028A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
01/12/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
RECEIVED (2) IN HOUSE BACKFLOW CERTIFICATIONS
01/10/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SHALL PROVIDE TRAFFIC RATED CLEANOUT COVERS IN CONVEYOR AREA & HAVE TRACER WIRE TO GRADE SOUTHSIDE
2. SHALL PROVIDE CORRECT BACKFLOW PROTECTION FOR
1 1/2 FEED TO CONVEYOR SYSTEM POTABLE COLD WATER WITH CERTIFICATION AND CERTIFICATION OF LANDSCAPING BACKFLOW DEVICE.
3. PUBLIC USE LAVS REQUIRE ADDITIONAL MEANS FOR HOT WATER SUPPLY NOT TO EXCEED 120 DEG. BESIDES THE WATER HEATER (TEMPERING VALVES)
10/10/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. SEE NOTE #2 & #3 AND COMPLY
PLUMBER TAPE IS NOT APPROVED FOR SECURING ANY MATERIALS.
2. ALL EXTERIOR CLEANOUTS TO BE TO GRADE AND HAVE TRAFFIC RATED COVERS IF REQUIRED.
3. MAKE WATER TIGHT JANITOR SINK. T&P TO TERMINATE OVER JANITOR SINK AND BE SECURED.
4. PROVIDE INFORMATION ON POSSIBLE NEED FOR BACKFLOW PROTECTION FOR 1 1/2 TO FEED EQUIPMENT (H20 SUPPLY)
09/21/2006 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. EXPOSE & PROVIDE ALL CLEANOUTS, PROVIDE TAPED PLUGS AND MACHINE SCREW WITH COVERS.
2. EXPOSE TRAP PRIMERS.
3. SECURE EXPANSION TANK. HAVE ALL OTHER PLUMBING INSPECTIONS APPROVED FOR FINAL.