Permit: T06CM00914

Parcel: 14103028A

Inspection Status: Approved

Inspection History: PLUMBING - YARD WTR LINE/TEST

Date Description Inspector Results Comments
09/19/2006 PLUMBING - YARD WTR LINE/TEST Approved IVRS - Inspection :*
09/15/2006 PLUMBING - YARD WTR LINE/TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*
INCREASE FROM 1" METER TO 2" COPPER IMMEDIATELY AFTER METER.
HIGH VELOCITY THROUGH 1" COPPER WILL LEAD TO PREMATURE FAILURE.
BLUE TRACER WIRE REQUIRED.
REMOVE EXCESS FLUX FROM SOLDER JOINTS. PIPING SHALL BE LAYED ON FIRM, COMPACTED GROUND. REMOVE LARGE CHUNKS. INSTALL HB VAC BREAKER.
07/26/2006 PLUMBING - YARD WTR LINE/TEST Partial Approval IVRS - Inspection :*
1" FROM NORTHWEST CORNER OUT TO LOADING DOCK HOSE BIB OK
1. NEED TO SEE FROM 2" STUB OUT OF BUILDING AT SOUTHWEST CORNER BACK TO RPB & METER
2. NEED TO SEE CORRECT CLOSET FLANGE INSTALLATION PRIOR TO SETTING STOOLS.