Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - ROUGH, SOIL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 09/26/2006 | PLUMBING - ROUGH, SOIL | Approved | IVRS - Inspection :* | |
| 05/02/2006 | PLUMBING - ROUGH, SOIL | Partial Approval | IVRS - Inspection :* WATER TEST WASTE & VENT FROM 2-WAY CLEANOUT THRU BUILDING UNDERGROUND ONLY OK 1. WILL NEED TO SEE PIPE WRAPS PRIOR TO CONCRETE AND TRAP PRIMERS. 2. SHALL REQUIRE WATER TEST THRU ROOF WHEN DRAINAGE FITTINGS ARE INSTALLED ON REVENT PIPING. YOUR REVENT ISOMETRIC IS APPROVED IN ERROR. 2" HORIZONTAL VENT PIPING CANNOT HANDLE THIS # OF FIXTURE UNITS. SEE 2003 UPC FOR CORRECT SIZING ON VENT FOR THIS INSTALLATION. |