Permit: T06CM00815

Parcel: 13314460A

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
04/10/2007 PLUMBING - FINAL Approved IVRS - Inspection :*
04/05/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
1. A DRY WELL WILL BE ACCEPTED FOR EXISTING T&P TERMINATIONS.
2. PROVIDE A VISIBLE AIR GAP AND A WAY TO AVOID DEBRIS FROM BLOCKING T&P.
3. ALL T&P RELIEF DRAINS MUST OPERATE W/OUT RESTRICTION.
4. FILL TUB 3118 FOR TEST
03/29/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
3036, 3015, 3035 - APP

NEED UNOBSTRUCTED T&P RELIEF DRAIN TERMINATIONS
POST UNIT #'S ON UNITS
SEE NOTES FROM PREVIOUS
03/28/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
3218, 3219 - LOW PSI
3220

3222 - CHECK T&P, FIX LEAK

OK 3120, 3121, 3122, 3221, 3223, 3217

3119 - SLOW DRAIN TUB
3118 - WET AT TUB
GAP AT DIVERTOR COVER
LOW WATER PSI

INSTALL HANDLES ON SERVICE VALVES
03/23/2007 PLUMBING - FINAL Partial Approval IVRS - Inspection :*
3124 FINAL OK
NO PROBLEM WITH PLUMBING THAT WOULD PREVENT TCO
03/22/2007 PLUMBING - FINAL Not ready for Inspection IVRS - Inspection :*
#3124 -- SHOWER DRAIN, DW HOSE
HAVE TUB FULL FOR RUN TEST
HAMMER ARRESTORS
CLEANOUT PLUGS