Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 04/20/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 04/11/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. FINISH PLAN REVISIONS AS PER PREVIOUS INSPECTION 2. LABEL CANOPY LIGHTING BREAKER 3. FILL UNUSED OPENING IN DEADFRONT 4. BREAKER TO BE LISTED FOR USE BY MANUFACTURE OK BUILDING TEMP C OF O |
|
| 04/09/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) NEED PLANS FOR SITE LIGHTING-SHOW LOAD CALC'S, ENERGY CALC'S AND OUTDOOR LIGHTING REQUIREMENT. WILL NEED FIXTURE SCHEDULES-THESE WILL BE FOR BOTH BLDG AND CANOPIES 2) FINISH 1 BEDROOMS |
|
| 04/05/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. RACEWAY TO PARKING CANOPY TO BE AS PER 300.5 2. NO MORE THAN 360 DEG. IN A CONDUIT RUN AS PER MEETINGS AND DISCUSSIONS ROOFTOP MAINTENANCE RECEPTACLES WILL NOT BE REQUIRED. IN LINEN CLOSETS A PLASTIC THERMOSTAT STYLE COVER WILL BE NEEDED OVER TRANSFORMERS -- ONE BEDROOM UNITS ONLY. |
|
| 03/29/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. ANCHOR STRAPS FOR FLEX TO BE EFFECTIVE - FIND STUD 2. BREAKERS TO BE LISTED BY MANUFACTURE 3. WATER HEATER DISCONNECTS NEEDED - ONE BEDROOM UNITS. 4. TRANSFORMERS IN LINEN CLOSETS. |
|
| 03/28/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BREAKER TO BE LISTED FOR USE BY MANUFACTURE 2. MISSING COVER PLATE - BLANK & DISCONNECT 3. WATER HEATER DISCONNECTING MEANS - 1 BEDROOM *TRANSFORMER IN LINEN CLOSET |
|
| 03/23/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* OK SALE OFFICE 1. WATER HEATER TO HAVE DISCONNECTING MEAN IF NOT WITHIN SITE 2. TIGHTEN FITTINGS |
|
| 03/22/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* 1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEEDS AN APPROVED EXTENDER RING 314.20 2. NO ABBREVIATIONS AT PANEL DIRECTORY 408.4 3. INSTALL CONNECTOR TO DISCONNECT 4. TIGHTEN LOOSE FITTINGS - HEATER 5. NEED ANTI-OXIDE COMPOUND ALL ALUMINUM CONDUCTORS 6. TRIM IN CLOTHES CLOSET TO BE CLOSED 7. SIZE TAP CONDUCTOR TO AMPACITY 8. REPAIR GROUNDING ELECTRODE CONDUCTOR 9. CAP OFF AND MAKE SAFE SITE LIGHTING 10. NEED MAINTENANCE RECEPTACLE 210.63 |