Permit: T06CM00815

Parcel: 13314460A

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
05/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
04/20/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
04/11/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. FINISH PLAN REVISIONS AS PER PREVIOUS INSPECTION
2. LABEL CANOPY LIGHTING BREAKER
3. FILL UNUSED OPENING IN DEADFRONT
4. BREAKER TO BE LISTED FOR USE BY MANUFACTURE

OK BUILDING TEMP C OF O
04/09/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) NEED PLANS FOR SITE LIGHTING-SHOW LOAD CALC'S, ENERGY CALC'S AND OUTDOOR LIGHTING REQUIREMENT. WILL NEED FIXTURE SCHEDULES-THESE WILL BE FOR BOTH BLDG AND CANOPIES
2) FINISH 1 BEDROOMS
04/05/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. RACEWAY TO PARKING CANOPY TO BE AS PER 300.5
2. NO MORE THAN 360 DEG. IN A CONDUIT RUN

AS PER MEETINGS AND DISCUSSIONS ROOFTOP MAINTENANCE RECEPTACLES WILL NOT BE REQUIRED. IN LINEN CLOSETS A PLASTIC THERMOSTAT STYLE COVER WILL BE NEEDED OVER TRANSFORMERS -- ONE BEDROOM UNITS ONLY.
03/29/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. ANCHOR STRAPS FOR FLEX TO BE EFFECTIVE - FIND STUD
2. BREAKERS TO BE LISTED BY MANUFACTURE
3. WATER HEATER DISCONNECTS NEEDED - ONE BEDROOM UNITS.
4. TRANSFORMERS IN LINEN CLOSETS.
03/28/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BREAKER TO BE LISTED FOR USE BY MANUFACTURE
2. MISSING COVER PLATE - BLANK & DISCONNECT
3. WATER HEATER DISCONNECTING MEANS - 1 BEDROOM

*TRANSFORMER IN LINEN CLOSET
03/23/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
OK SALE OFFICE
1. WATER HEATER TO HAVE DISCONNECTING MEAN IF NOT WITHIN SITE
2. TIGHTEN FITTINGS
03/22/2007 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
1. BOXES MORE THAN 1/4" FROM BOX TO SURFACE NEEDS AN APPROVED EXTENDER RING 314.20
2. NO ABBREVIATIONS AT PANEL DIRECTORY 408.4
3. INSTALL CONNECTOR TO DISCONNECT
4. TIGHTEN LOOSE FITTINGS - HEATER
5. NEED ANTI-OXIDE COMPOUND ALL ALUMINUM CONDUCTORS
6. TRIM IN CLOTHES CLOSET TO BE CLOSED
7. SIZE TAP CONDUCTOR TO AMPACITY
8. REPAIR GROUNDING ELECTRODE CONDUCTOR
9. CAP OFF AND MAKE SAFE SITE LIGHTING
10. NEED MAINTENANCE RECEPTACLE 210.63