Permit: T06CM00756

Parcel: 110035400

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/29/2008 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/27/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
PROVIDE BUSHINGS AS NOTED PREVIOUSLY
08/26/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
NO ACCESS
DEAN, PLEASE LEAVE YOUR PHONE NUMBER ON MESSAGE
07/18/2008 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
1. PROVIDE BUSHINGS WHERE CARFLEX PENETRATES KNOCKOUT HOLES IN EXHAUST FANS & HP2
2. MARK UNIT DATA PLATE W/PROPER HEAT STRIP & FUSE ACCORDINGLY
3. I.D EQUIPMENT WITH SUITE NUMBER
4. DATA PLATE FOR HP3 IS BLOCKED BY ENERGY RECOVERY UNIT
5. DUCT SMOKE DETECTORS NOT REQUIRED
6. PROVIDE AIR BALANCE FOR EF-1 & EF-3
7. BE SURE TO INTERLOCK WITH AC UNITS AS REQUIRED
8. PROVIDE THE LISTED COVER FOR CONDENSOR
06/20/2008 MECHANICAL - FINAL Cancelled IVRS - RI canceled
05/06/2008 MECHANICAL - FINAL Not ready for Inspection IVRS - Inspection :*
- PROVIDE AIR BALANCE REPORT
- NEED TO TEST DUCT SMOKE DETECTORS
- PROVIDE PERMANENT ACCESS TO ROOFTOP IF OVER 16' FROM GRADE
03/21/2008 MECHANICAL - FINAL Denied IVRS - Inspection :
There is no access to the site.| 920*
DOORS LOCKED