Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/29/2008 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/27/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* PROVIDE BUSHINGS AS NOTED PREVIOUSLY |
|
| 08/26/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* NO ACCESS DEAN, PLEASE LEAVE YOUR PHONE NUMBER ON MESSAGE |
|
| 07/18/2008 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* 1. PROVIDE BUSHINGS WHERE CARFLEX PENETRATES KNOCKOUT HOLES IN EXHAUST FANS & HP2 2. MARK UNIT DATA PLATE W/PROPER HEAT STRIP & FUSE ACCORDINGLY 3. I.D EQUIPMENT WITH SUITE NUMBER 4. DATA PLATE FOR HP3 IS BLOCKED BY ENERGY RECOVERY UNIT 5. DUCT SMOKE DETECTORS NOT REQUIRED 6. PROVIDE AIR BALANCE FOR EF-1 & EF-3 7. BE SURE TO INTERLOCK WITH AC UNITS AS REQUIRED 8. PROVIDE THE LISTED COVER FOR CONDENSOR |
|
| 06/20/2008 | MECHANICAL - FINAL | Cancelled | IVRS - RI canceled | |
| 05/06/2008 | MECHANICAL - FINAL | Not ready for Inspection | IVRS - Inspection :* - PROVIDE AIR BALANCE REPORT - NEED TO TEST DUCT SMOKE DETECTORS - PROVIDE PERMANENT ACCESS TO ROOFTOP IF OVER 16' FROM GRADE |
|
| 03/21/2008 | MECHANICAL - FINAL | Denied | IVRS - Inspection : There is no access to the site.| 920* DOORS LOCKED |