Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2008 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 08/08/2008 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/05/2008 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* PLEASE HAVE ELECTRICAL CONTR. ON SITE NEXT INSP. |
|
| 06/20/2008 | ELECTRIC - FINAL | Cancelled | IVRS - RI canceled | |
| 05/02/2008 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. LABEL TIME CLOCK & CONTACTOR 2. CONTACTOR ENCLOSURE NOT BONDED 3. TIME CLOCK IMPROPERLY WIRED 4. LIGHTING NOT AS PER PLANS - ALSO EM LIGHTING 5. CHECK SERVICE AND ROOF AND EXTERIOR NEXT TIME 1. MAINTAIN WORKING CLEARANCES AT DISCONNECTS 2. SEAL WALK-IN PER 300.7 3. PROTECT CONDUCTORS FROM SHARP METAL EDGES 4. USE APPROVED EXTENDER RINGS - METAL NOT APPROVED 314.20 AND AT COMBUSTIBLES 5. LABEL PANEL DIRECTORY AS PER 408.4 6. PLEASE VERIFY LISTING FOR DIVIDERS FOR USE WITH INDUSTRIAL COVERS 7. FILL UNUSED BREAKER OPENINGS 8. MOUNT DEVICES TO BOXES |