Permit: T06CM00756

Parcel: 110035400

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/12/2008 ELECTRIC - FINAL Approved IVRS - Inspection :*
08/08/2008 ELECTRIC - FINAL Not ready for Inspection IVRS - Inspection :*
08/05/2008 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
PLEASE HAVE ELECTRICAL CONTR. ON SITE NEXT INSP.
06/20/2008 ELECTRIC - FINAL Cancelled IVRS - RI canceled
05/02/2008 ELECTRIC - FINAL Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. LABEL TIME CLOCK & CONTACTOR
2. CONTACTOR ENCLOSURE NOT BONDED
3. TIME CLOCK IMPROPERLY WIRED
4. LIGHTING NOT AS PER PLANS - ALSO EM LIGHTING
5. CHECK SERVICE AND ROOF AND EXTERIOR NEXT TIME

1. MAINTAIN WORKING CLEARANCES AT DISCONNECTS
2. SEAL WALK-IN PER 300.7
3. PROTECT CONDUCTORS FROM SHARP METAL EDGES
4. USE APPROVED EXTENDER RINGS - METAL NOT
APPROVED 314.20 AND AT COMBUSTIBLES
5. LABEL PANEL DIRECTORY AS PER 408.4
6. PLEASE VERIFY LISTING FOR DIVIDERS FOR USE WITH INDUSTRIAL COVERS
7. FILL UNUSED BREAKER OPENINGS
8. MOUNT DEVICES TO BOXES