Permit: T06CM00756

Parcel: 110035400

Inspection Status: Approved

Inspection History: ELECTRIC - ABOVE CEILING

Date Description Inspector Results Comments
08/12/2008 ELECTRIC - ABOVE CEILING Approved IVRS - Inspection :*
01/28/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK TO TILE

FINISH #1, #2, #3
01/23/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. INSTALL GROUNDING ELECTRODE TAPS
2. BRACE CABLES AS PER MANUFACTURES INSTRUCTIONS
3. FINISH PREVIOUS ITEMS: 1, 2, 3, 5 OF 1/16/08 INSP.

A REFEE MAY BE ASSESSED IF WORK IS NOT COMPLETED
01/16/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. USE APPROVED SIZED LUGS FOR CONDUCTORS
2. BONDING JUMPERS TO BE SIZED PER 250.66
3. INSTALL MAIN BONDING JUMPERS
4. INSTALL REJECTION PINS
5. LABEL SERVICE EQUIPMENT
6. FINISH PREVIOUS ITEMS
01/14/2008 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
1. MANUFACTURES CLIPS TO BE EFFECTIVE
2. TERMINATE ALL CONDUCTORS
3. CLEAN EXCESS DIRT & TRASH FROM PANELS
4. CLOSE ALL BOXES - DEVICE & PLATE FOR TEMP POWER
5. LABEL SERVICE EQUIPMENT
6. A BOND WILL BE NEEDED FOR TEMP POWER

OK TO COVER PVC
DATA & POWER
01/11/2008 ELECTRIC - ABOVE CEILING Cancelled IVRS - RI canceled
01/03/2008 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
See detailed listing on site.| 999*
PARTIAL INSPECTION - WORK INCOMPLETE

1. LOW VOLTAGE WIRING TO BE SUPPORTED TO BUILDING STRUCTURE/RAN IN A NEAT & WORKMANLIKE MANNER
2. ALL FIXTURES & EXIT SIGNS TO HAVE SUPPORT WIRES
3. WIRE NUTS TO BE USED PER INSTUCTIONS ON BAG
4. SECURE MC WITHIN 12" OF TERMINATIONS AND AT 6' INTERVALS
5. HAVE OVERFILLED J-BOX
6. SECURE EMT WITHIN 36" OF ENCLOSURES
7. MAX 360 DEG. OF BENDS IN RACEWAYS
8. STRAPS FOR RACEWAYS TO SCREW INTO STRUCTURE OR USE ANCHORS
9. LECTURE ROOM CEILING NOT COMPLETE
11/08/2007 ELECTRIC - ABOVE CEILING Cancelled IVRS - RI canceled
11/06/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
There is no access to the site.| 920*
10/30/2007 ELECTRIC - ABOVE CEILING Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
08/29/2007 ELECTRIC - ABOVE CEILING Partial Approval IVRS - Inspection :*
OK DOWNSTAIRS HARD LIDS
1. FINISH UPSTAIRS
2. NOTE: NO MORE THAN 360 DEG. IN CONDUIT RUNS
08/28/2007 ELECTRIC - ABOVE CEILING Not ready for Inspection IVRS - Inspection :*
SECURE M/C CABLE WITHIN 12" OF CAN BOXES 330.30