Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/12/2008 | ELECTRIC - ABOVE CEILING | Approved | IVRS - Inspection :* | |
| 01/28/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK TO TILE FINISH #1, #2, #3 |
|
| 01/23/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. INSTALL GROUNDING ELECTRODE TAPS 2. BRACE CABLES AS PER MANUFACTURES INSTRUCTIONS 3. FINISH PREVIOUS ITEMS: 1, 2, 3, 5 OF 1/16/08 INSP. A REFEE MAY BE ASSESSED IF WORK IS NOT COMPLETED |
|
| 01/16/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* 1. USE APPROVED SIZED LUGS FOR CONDUCTORS 2. BONDING JUMPERS TO BE SIZED PER 250.66 3. INSTALL MAIN BONDING JUMPERS 4. INSTALL REJECTION PINS 5. LABEL SERVICE EQUIPMENT 6. FINISH PREVIOUS ITEMS |
|
| 01/14/2008 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1. MANUFACTURES CLIPS TO BE EFFECTIVE 2. TERMINATE ALL CONDUCTORS 3. CLEAN EXCESS DIRT & TRASH FROM PANELS 4. CLOSE ALL BOXES - DEVICE & PLATE FOR TEMP POWER 5. LABEL SERVICE EQUIPMENT 6. A BOND WILL BE NEEDED FOR TEMP POWER OK TO COVER PVC DATA & POWER |
|
| 01/11/2008 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
| 01/03/2008 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : See detailed listing on site.| 999* PARTIAL INSPECTION - WORK INCOMPLETE 1. LOW VOLTAGE WIRING TO BE SUPPORTED TO BUILDING STRUCTURE/RAN IN A NEAT & WORKMANLIKE MANNER 2. ALL FIXTURES & EXIT SIGNS TO HAVE SUPPORT WIRES 3. WIRE NUTS TO BE USED PER INSTUCTIONS ON BAG 4. SECURE MC WITHIN 12" OF TERMINATIONS AND AT 6' INTERVALS 5. HAVE OVERFILLED J-BOX 6. SECURE EMT WITHIN 36" OF ENCLOSURES 7. MAX 360 DEG. OF BENDS IN RACEWAYS 8. STRAPS FOR RACEWAYS TO SCREW INTO STRUCTURE OR USE ANCHORS 9. LECTURE ROOM CEILING NOT COMPLETE |
|
| 11/08/2007 | ELECTRIC - ABOVE CEILING | Cancelled | IVRS - RI canceled | |
| 11/06/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : There is no access to the site.| 920* |
|
| 10/30/2007 | ELECTRIC - ABOVE CEILING | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* |
|
| 08/29/2007 | ELECTRIC - ABOVE CEILING | Partial Approval | IVRS - Inspection :* OK DOWNSTAIRS HARD LIDS 1. FINISH UPSTAIRS 2. NOTE: NO MORE THAN 360 DEG. IN CONDUIT RUNS |
|
| 08/28/2007 | ELECTRIC - ABOVE CEILING | Not ready for Inspection | IVRS - Inspection :* SECURE M/C CABLE WITHIN 12" OF CAN BOXES 330.30 |