Permit: T06CM00756

Parcel: 110035400

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/12/2008 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
11/09/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CONDUITS WITH OVER 360 DEG. TO HAVE CEILING J-BOXES INSTALLED, WILL CHECK ON CEILING INSPECTION
OK WALL COVER
11/08/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
FINISH PREVIOUS ITEMS
11/06/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
There is no access to the site.| 920*
LOCKED NO ACCESS
10/30/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. PROTECT VDV CABLES IN WALLS FROM SHARP METAL EDGES
2. SUPPORT VDV CABLES IN WALLS & FLOOR
3. NO MORE THAN 360 DEG. IN CONDUIT RUNS
4. SUPPORT M/C CABLE WITHIN 12" OF BOXES
5. TIGHTEN LOOSE FITTINGS
6. WE HAVE BOXES OVERFILLED
7. SUPPORT CONDUITS ABOVE PANELS
8. PROTECT M/C CABLES IN STUD CHANNELS
9. FILL UNUSED OPENINGS
09/20/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) NO INTERMEDIATE WORK DONE
09/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK LECTURE ROOM RECEPTACLES-CHECK REVISION FOR ADDITIONAL OUTLETS
09/04/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK UPSTAIRS LIDS
08/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS
08/21/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1. PROTECT M/C CABLE IN CHANNELS OF STUDS
2. FINISH PREVIOUS ITEMS 1, 5 & 7

RECEIVED LETTER FROM MC CONDUITS & FITTINGS
08/20/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
1) CANCELLED
08/16/2007 ELECTRIC - INTERMEDIATE Denied IVRS - Inspection :
The wiring is not complete or does not comply with code.| 245*
1. SECURE MC CABLE WITHIN 12" OF BOXES -- 330.30
2. GROUND ALL METAL JUNCTION BOXES
3. PREVENT DI-ELECTRIC CONTACT
4. PROVIDE BACK BRACING TO PREVENT BOX MOVEMENT
5. TIGHTEN LOOSE FITTINGS & FULLY SEAT FITTINGS
6. PLANS CALL FOR 3/4" EMT MINIMUM & COMPRESSION FITTING
7. PROTECT PVC CONDUITS AT BASE PLATE
8. NEED AUTHORIZATION TO USE MC & PVC IN WALLS
08/15/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
CANCELLED