Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/20/2006 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 03/17/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/15/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* CANCELLED BY DAVE |
|
| 03/14/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1. PLEASE LABEL ALL DISCONNECTS AND A PERMANENT METAL ADDRESS LABEL IS NEEDED. 2. CORRECTLY IDENTIFY HIGH LEG AS PER 215.8, 230.56, 110.15, 408.3 (E) 3. SPLIT BOLTS ONLY LISTED FOR 2 CONDUCTORS - A RUN & A TAP 4. VERIFY GROUNDING ELECTRODE CONDUCTOR. IF IT IS INSTALLED IN A RACEWAY. USE 250.64 (E) 5. WE HAVE MORE THAN 6 DISCONNECTS 230.71 |
|
| 03/08/2006 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* GROUNDING SCREW MISSING AT 4 GAUGE BOX INSTALL ALL GROUNDING SCREWS PRIOR TO ABOVE CEILING INSP. |
|
| 03/03/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* DUE TO THE AMOUNT OF WORK ASKED FOR AT SERVICE AND THE CONDITION OF EXISTING SERVICE EQUIPMENT PLEASE HAVE ENGINEER ASSESS WHAT IS TO BE DONE. |
|
| 03/02/2006 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* 1) SUPPORT UDV CABELING IN WALLS |