Permit: T06CM00594

Parcel: 127121230


Addresses:

5645 E BROADWAY BL

Inspection Status: Approved

Inspection History: REINFORCED MASONRY PRE-GROUT

Date Description Inspector Results Comments
03/20/2006 REINFORCED MASONRY PRE-GROUT Approved IVRS - Inspection :*
OBSERVED INSTALLATION OF EPOXY BOLTS
03/17/2006 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1. NEED SIMPSON SET EPOXY (I.C.B.O #ER-5279) PER LESTER FROM STRUCTURAL ENGINEER
03/16/2006 REINFORCED MASONRY PRE-GROUT Partial Approval IVRS - Inspection :*
MASONRY OK
NEED TO VERIFY EPOXY BOLT INSTALLATION
03/13/2006 REINFORCED MASONRY PRE-GROUT Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PLEASE PROVIDE STAMPED LETTER FROM ENGINEER STATING THAT THROUGH BOLTS ARE ACCEPTABLE IN LIEU OF EPOXY BOLTS
2) PLEASE PROVIDE TYPE OF EPOXY DESIGNATED BY ENGINEER IF EPOXY BOLTS ARE REQUIRED
3) NEED WELDER'S CERTIFICATIONS FOR ANY FIELD WELDING DONE ON STEEL LINTEL EXTENSIONS
03/07/2006 REINFORCED MASONRY PRE-GROUT Not ready for Inspection IVRS - Inspection :*
1. NEED CLARIFICATION FOR KEYNOTE 12 ON DETAIL SKI ON SHEET S1
2. NEED STAMPLED LETTER FROM ENGINEER STATING THAT THROUGH BOLTS ARE ACCEPTABLE IN LIEU OF EPOXY BOLTS (KEYNOTE 13)