Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - ABOVE CEILING
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/07/2007 | MECHANICAL - ABOVE CEILING | Approved | IVRS - Inspection :* CHECKED REMAINING CONDENSATE DRAINS OK TO INSULATE OK FOR REMAINING CEILING TILES |
|
| 04/09/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* 1) OK FOR CEILING TILES ALL AREAS EXCEPT HALLWAY 2) NEED TO SEE CONDENSATE DRAIN LINES FROM UNITS 11, 12 & 13 |
|
| 03/07/2007 | MECHANICAL - ABOVE CEILING | Partial Approval | IVRS - Inspection :* CHECKED SEALED JOINTS ON DUCT WORK. OK TO INSULATE. MIN. R5 DUCT WRAP IS REQUIRED. 1 1/2" IS R4.2 REVISE PLANS OF DELETING ANY FIRE DAMPERS. |