Permit: T06CM00288

Parcel: 141185330


Addresses:

9608 E OLD VAIL RD

Inspection Status: Approved

Inspection History: ELECTRIC - FINAL

Date Description Inspector Results Comments
08/02/2007 ELECTRIC - FINAL Approved IVRS - Inspection :*
07/26/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. INSTALL 6 TERMINAL POLARIS LUGS AT BATTERY
JUNCTION BOX
2. PROVIDE AMPACITY INFORMATION ON 4/0 POWER CABLE.
07/09/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK PANELS IN DISHES
2. OK OUTSIDE LIGHTS & POLE LIGHTS

OK TO FILE FOR TEMP C OF O
06/18/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK CONDENSOR AREA FOR CRAC UNITS
2. MISSING OUTDOOR LIGHTS & NEED TO FINISH CAMERA MAKEUP
3. PANELS AT DISHES BEING FED WITH 200A PANEL MARKED 100A MAX.
4. CONNECT PANELS AT DISHES TO GROUNDING ELECTRODES AT DISHES 250.32
5. NEED TO INSTALL PANEL AT SERVICES DESCRIBING ALL LOCATIONS OF DIFFERENT SERVICES & POWER SUPPLIES.
06/14/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
06/13/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1) INSTALL DISCONNECT FOR WATER HEATER
2) SOME RECEPTACLES HAVE NO POWER
3) GROUNDING OF BATTERY RACKS AND CABLE TRAY IN BATTERY ROOM
4) 800 AMP DISCONNECT REATED FOR 600 V AC NOT DC
5) INSTALL ARC FLUSH WARNINGS ON SWITCH BOARDS, PANEL BOARD, ETC... NEC 110.16
05/21/2007 ELECTRIC - FINAL Partial Approval IVRS - Inspection :*
1. OK 2000 AMP SWITCH OUTSIDE BUILDING FOR GEN A
2. OK GEN A & GEN B
3. OK PANEL DPUPA & DPUPB
4. OK FINALS ON 3 OFFICES