Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/02/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* | |
| 07/26/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. INSTALL 6 TERMINAL POLARIS LUGS AT BATTERY JUNCTION BOX 2. PROVIDE AMPACITY INFORMATION ON 4/0 POWER CABLE. |
|
| 07/09/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK PANELS IN DISHES 2. OK OUTSIDE LIGHTS & POLE LIGHTS OK TO FILE FOR TEMP C OF O |
|
| 06/18/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK CONDENSOR AREA FOR CRAC UNITS 2. MISSING OUTDOOR LIGHTS & NEED TO FINISH CAMERA MAKEUP 3. PANELS AT DISHES BEING FED WITH 200A PANEL MARKED 100A MAX. 4. CONNECT PANELS AT DISHES TO GROUNDING ELECTRODES AT DISHES 250.32 5. NEED TO INSTALL PANEL AT SERVICES DESCRIBING ALL LOCATIONS OF DIFFERENT SERVICES & POWER SUPPLIES. |
|
| 06/14/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* | |
| 06/13/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1) INSTALL DISCONNECT FOR WATER HEATER 2) SOME RECEPTACLES HAVE NO POWER 3) GROUNDING OF BATTERY RACKS AND CABLE TRAY IN BATTERY ROOM 4) 800 AMP DISCONNECT REATED FOR 600 V AC NOT DC 5) INSTALL ARC FLUSH WARNINGS ON SWITCH BOARDS, PANEL BOARD, ETC... NEC 110.16 |
|
| 05/21/2007 | ELECTRIC - FINAL | Partial Approval | IVRS - Inspection :* 1. OK 2000 AMP SWITCH OUTSIDE BUILDING FOR GEN A 2. OK GEN A & GEN B 3. OK PANEL DPUPA & DPUPB 4. OK FINALS ON 3 OFFICES |