Permit: T06CM00288

Parcel: 141185330


Addresses:

9608 E OLD VAIL RD

Inspection Status: Approved

Inspection History: ELECTRIC - INTERMEDIATE

Date Description Inspector Results Comments
08/02/2007 ELECTRIC - INTERMEDIATE Approved IVRS - Inspection :*
06/18/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
06/14/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK TEKO ROOM, NOC ROOM, PANTRY, BATHROOMS, SWITCHGEAR ROOM AND LOADING DOCK
2) INSTALL K.O. SEALS IN SMOKE DETECTOR BOXES IN MER FLOOR
3) NEED REVISED DRAWINGS FOR BATTERY ROOMS
4) LABEL ALL PANELS, DISCONNECTS AND INSTALL PANEL DIRECTORIES
5) FLEXIBLE POWER CABLE USED IN BATTERY ROOMS NEEDS TO TERMINATE IN LUGS LISTED FOR FLEXIBLE CABLE NEC 400 & 110.3
06/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/21/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/07/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
05/03/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK PANELS EAST & WEST ENDS OF MAIN EQUIPMENT ROOM
2. OK 112.5 KVA & 75 KVA TRANSFORMERS IN MAIN SW GEAR ROOMS A & B
3. OK 4 225 KVA TRANSFORMERS
4. OK PANELS UPB, UPA, DPTB1, DPTB2, DPTA1, DPTA2
04/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK MECH A, MECH B, DPA, DPB, LPA, LPB, PPA, PPB
2. OK MIDDLE ROW OF PANELS IN MECH. EQUIPMENT ROOM
3. BONDING JUMPER FROM TRANSFORMERS TO FIRST DISCONNECT ON SECONDARY TO BE SIZED PER NEC 250.30 A5 500 MCM TO BE 1/6 250 MCM TO BE #2
04/23/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
04/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
CHECKED LOCK OUT OF MAIN SERVICE DISCONNECT
LOCK OUT ON BUTTON ALSO
04/17/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1) OK GFI TEST REPAORT MAIN SWITCH GEAR A & B
2) COMPLETE ITEMS FROM INSPECTION ON 4/13/07
3) INSTALL LOCK OUT AS DISCUSSED ON 4/13/07. POWER UP TO MAIN BREAKER ONLY. MAIN BREAKER TO BE LOCKED OUT
04/13/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. OK CEILINGS RMS 101, 102, 103 & 121
2. NEED TO BOND WATER, STEEL & SPRINKLER TO SERVICES
3. PROVIDE LETTER OF TORQUE
4. RECALL FOR FEEDERS TO PANELS, ETC
5. NEED INSTRUCTION MANUAL FOR SWITCH GEAR
6. NEED PERFORMANCE TEST OF SWITCHGEAR GFCI
7. OK GROUND RING AROUND BUILDING.
04/11/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
03/19/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
1. MAIN EQUIPMENT ROOM 119 UNDER FLOOR FROM CENTER PANELS TO GUTTERS.
2. WALLS IN FOLLOWING ROOMS 118, MAIN SERVICE A
MAIN SERVICE B OK
03/15/2007 ELECTRIC - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NO ONE ON SITE TO DIRECT TO INSPECTION AREA
03/06/2007 ELECTRIC - INTERMEDIATE Partial Approval FOLLOWING ROOMS OK TO COVER

102, 103, 104, 105, 106, 107, 108, 110, 111, 112, 113, 114, 115
02/26/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
OK WALLS TEC CO ROOM & OUTSIDE PERIMETER
WEST & NORTH
02/22/2007 ELECTRIC - INTERMEDIATE Partial Approval IVRS - Inspection :*
LOADING DOCK RM 122, MAIN EQM'T ROOM 119
OK TO COVER