Permit: T06CM00288

Parcel: 141185330


Addresses:

9608 E OLD VAIL RD

Inspection Status: Approved

Inspection History: EXCAVATION/LAYOUT REBAR & ZON

Date Description Inspector Results Comments
06/13/2007 EXCAVATION/LAYOUT REBAR & ZON Approved IVRS - Inspection :*
05/25/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
7 LIGHT POLE BASES AS PER PLANS
05/23/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1ST LIFT @ EAST SCREEN WALLS W/LAPS
05/17/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
SCREEN WALL FOOTING/STEM WALL NORTHWEST
CORNER @ GENERATOR -- FUEL TANKS.
03/21/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
SOUTH STAIRS - STEP FORMS REINFORCING STEEL
NORTH CARPORT COLUMN FOOTINGS -- 6 TOTAL
03/13/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
TWO EAST SIDE GENERATOR PADS & 1 FUEL TANK PAD
03/08/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
1. STAIR FORMING @ GRID LINE C BETWEEN 2 & 3
2. STAIR FORMING @ GRID LINE C-7 EAST END OF BLDG
03/07/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
WEST STAIRS (STEP REINFORCEMENT) AS PER SHEET
S3.D DETAIL #105
03/02/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
F7 COLUMNS @ PARKING CANOPY
03/01/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
SOUTH & WEST STAIR WALLS AS PER DETAIL #107
ON SHEET S3.0
02/26/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
EAST CANOPY COLUMNS FOOTINGS (12) EQUIP. YARD
SOUTH SIDE STAIR FOOTING & WEST SIDE STAIR FOOTING
01/30/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
BOTH ANTENNA FOUNDATIONS -- OK TO POUR
01/26/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
DRYPACK AT GRID #1 A & E AND GRID #7 E
NOTE: COLUMN @ GRID #7-D NOT DRY PACKED

DAVID SCHWANKE
19681 PHOENIX LANE
HUNTINGTON BEACH, CA 92646
714-964-7410
FAX 714-964-4040
01/03/2007 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
TOTAL OF 11
DRY PAC AT STEEL COLUMN BASES AT GRID LINE "A"
2 THRU 7 - AT GRID "1" B THRU D & AT GRID "7" AT B & C

NOTE: REVISED APPROVED PLANS CONFIRM INSTALLED REINFORCING STEEL THAT WAS INSPECTED ON 12/6/2006 AS CORRECT AND IN AGREEMENT W/NEW PLANS SHEET S1.1
01/02/2007 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
CANCELLED BY CONTRACTOR
12/06/2006 EXCAVATION/LAYOUT REBAR & ZON Partial Approval IVRS - Inspection :*
OBSERVATION INSPECTION - PARTIAL APPROVAL

OK TO POUR MAIN BUILDING PERIMETER AND COLUMN FOOTINGS AS PER NOTE BELOW -- AWAITING NEW APPROVED PLANS WHICH MUST MATCH OBSERVATION NOTES.

NOTE #1:
1. PERIMETER FOOTING F-6 - 2 #5'S CONTINUOUS W/1 #4 @ 24"
O.C AND #5 VERTICALS @ 48" O.C
2. PERIMETER & INTERIOR BEARING F- 5 FOOTINGS - 2- #5 CONTINUOUS T & B W/1 #4 @ 24" O.C
3. F-1 COLUMN FOOTINGS - 4 - #4'S EACH WAY -
2'6"X2'6" (8 EACH)
4. F-2 COLUMN FOOTINGS - 5 - #4'S EACH WAY
3'6" X 3'6" (7 EACH)
5. F-3 COLUMN FOOTINGS - 4 - #4'S EACH WAY
3'0" X 3'0" (5 EACH)
6. F-4 COLUMN FOOTINGS - 4- #5'S EACH WAY
4'6" X 4'6" (5 EACH

NOTE #2:
REINFORCING STEEL IN ABOVE FOOTINGS MUST MATCH THE SCHEDULE ON THE NEW PLANS WHEN THEY ARE APPROVED BY THE CITY.

ABOVE INSPECTION CONDUCTED
PER JESSE SANDERS - PROCEED AT OWN RISK
12/04/2006 EXCAVATION/LAYOUT REBAR & ZON Not ready for Inspection IVRS - Inspection :*
WAITING ON NEW APPROVED PLANS.