Inspection History Details
Inspection Status: Approved
Inspection History: MECHANICAL - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/06/2007 | MECHANICAL - FINAL | Approved | IVRS - Inspection :* | |
| 08/02/2007 | MECHANICAL - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* - PROVIDE PROPER SIZE REDUCER WASHERS AT CONNECTION TO AC UNIT 3 - PROVIDE A ROOF JACK AT CONDENSATE PENETRATION THRU ROOF. - PROPERLY IDENTIFY CONDUCTORS USED FOR AC 3 - PROVIDE VIBRATION ISOLATORS - SECURE ELEC. CONDUITS CONDENSORS 1 & 2 NOT FUSED CORRECTLY |
|
| 07/25/2007 | MECHANICAL - FINAL | Partial Approval | IVRS - Inspection :* REPLACE CRACKED CONDENSATE PIPING UNIT 2 PROVIDE FUSES IN ELEC. DISCONNECTS PERMANENTLY I.D CONDENSORS PROVIDE VIBRATION ISOLATORS FINISH INSTALLING PACKAGE UNIT |