Permit: T06CM00236

Parcel: 12214018A

Inspection Status: Approved

Inspection History: MECHANICAL - FINAL

Date Description Inspector Results Comments
08/06/2007 MECHANICAL - FINAL Approved IVRS - Inspection :*
08/02/2007 MECHANICAL - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
- PROVIDE PROPER SIZE REDUCER WASHERS AT CONNECTION TO AC UNIT 3
- PROVIDE A ROOF JACK AT CONDENSATE PENETRATION
THRU ROOF.
- PROPERLY IDENTIFY CONDUCTORS USED FOR AC 3
- PROVIDE VIBRATION ISOLATORS
- SECURE ELEC. CONDUITS

CONDENSORS 1 & 2 NOT FUSED CORRECTLY
07/25/2007 MECHANICAL - FINAL Partial Approval IVRS - Inspection :*
REPLACE CRACKED CONDENSATE PIPING UNIT 2
PROVIDE FUSES IN ELEC. DISCONNECTS
PERMANENTLY I.D CONDENSORS
PROVIDE VIBRATION ISOLATORS
FINISH INSTALLING PACKAGE UNIT