Permit: T06CM00236

Parcel: 12214018A

Inspection Status: Approved

Inspection History: PLUMBING - SEWER HCS CONNECT

Date Description Inspector Results Comments
05/22/2007 PLUMBING - SEWER HCS CONNECT Approved IVRS - Inspection :*
02/13/2007 PLUMBING - SEWER HCS CONNECT Partial Approval IVRS - Inspection :*
SPECIAL INSP. PER STEVE
HCS CONNECTION OK
SEWER PIPING OK TO COVER
02/01/2007 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
THERE IS PLENTY FALL AVAILABLE
PROVIDE UNIFORM SLOPE THROUGHOUT
YOU HAVE 2 SECTIONS WITH BACK PITCH, 2 SECTIONS THAT ARE FLAT
MANY AREAS HAVE 1/8" PER SLOPE, SOME SECTIONS HAVE NEARLY 1" PER FOOT-2 PERCENT IS MINIMUM REQUIRED SLOPE UNLESS PRIOR APPROVAL IS GRANTED ON PLANS
01/26/2007 PLUMBING - SEWER HCS CONNECT Denied IVRS - Inspection :
See detailed listing on site.| 999*
REQUEST HOLD OVER TILL TOM ORRO
DITCH NOT DEEP ENOUGH

1. SITE PLAN DOES NOT HAVE MECHANICAL PLANS
EXAMINER STAMP.
2. BACKPITCH 2 LOCATIONS
FLAT AT LEAST 2 LOCATIONS
PAY ATTENTION TO BOW OF PIPING
PROVIDE UNIFORM SLOPE THROUGHOUT, MIN 1/4"
PROVIDE CLEANOUT SHOWN AT 100'
3. PROVIDE 4" CLEANOUTS AT UPPER END PER P-1 SEWER DIAGRAM.
4. REDLINE CHANGE OF BUILDING DRAINS LOCATION
FOR UNIT B