Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - SEWER HCS CONNECT
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2007 | PLUMBING - SEWER HCS CONNECT | Approved | IVRS - Inspection :* | |
| 02/13/2007 | PLUMBING - SEWER HCS CONNECT | Partial Approval | IVRS - Inspection :* SPECIAL INSP. PER STEVE HCS CONNECTION OK SEWER PIPING OK TO COVER |
|
| 02/01/2007 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* THERE IS PLENTY FALL AVAILABLE PROVIDE UNIFORM SLOPE THROUGHOUT YOU HAVE 2 SECTIONS WITH BACK PITCH, 2 SECTIONS THAT ARE FLAT MANY AREAS HAVE 1/8" PER SLOPE, SOME SECTIONS HAVE NEARLY 1" PER FOOT-2 PERCENT IS MINIMUM REQUIRED SLOPE UNLESS PRIOR APPROVAL IS GRANTED ON PLANS |
|
| 01/26/2007 | PLUMBING - SEWER HCS CONNECT | Denied | IVRS - Inspection : See detailed listing on site.| 999* REQUEST HOLD OVER TILL TOM ORRO DITCH NOT DEEP ENOUGH 1. SITE PLAN DOES NOT HAVE MECHANICAL PLANS EXAMINER STAMP. 2. BACKPITCH 2 LOCATIONS FLAT AT LEAST 2 LOCATIONS PAY ATTENTION TO BOW OF PIPING PROVIDE UNIFORM SLOPE THROUGHOUT, MIN 1/4" PROVIDE CLEANOUT SHOWN AT 100' 3. PROVIDE 4" CLEANOUTS AT UPPER END PER P-1 SEWER DIAGRAM. 4. REDLINE CHANGE OF BUILDING DRAINS LOCATION FOR UNIT B |