Permit: T06CM00236

Parcel: 12214018A

Inspection Status: Approved

Inspection History: PLUMBING - INTERMEDIATE

Date Description Inspector Results Comments
05/22/2007 PLUMBING - INTERMEDIATE Approved IVRS - Inspection :*
05/17/2007 PLUMBING - INTERMEDIATE Partial Approval IVRS - Inspection :*
ABS TEST WAS NOT TO ROOF, POSSIBLE LEAK AT WEST WC
WATER PIPING REDUCES FROM 1 1/2 TO 3/4,
3/4 THEN SUPPLIES ALL FIXTURES
THIS DOES NOT APPEAR TO MEET PLANS
ALSO, 3/4 IS SHOWN TO EACH FIXTURE
1 1/2 IS SHOWN TO WATER HEATER
- IT IS NOT CLEAR WHAT SIZE IS COMING OUT OF WH AND IS NOT CLEAR HOW IT IS REDUCED.

PROVIDE SCHEMATIC FOR CLARIFICATION OF SIZING.
OK TO INSULATE ALL AREAS EXCEPT AT POSSIBLE LEAK AND AT WATER CHANGES.
05/15/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
TEST TO BE THRU ROOF
NO LEAKS ON TUBS
WATER PIPING TO BE PER PLAN & SPEC
05/14/2007 PLUMBING - INTERMEDIATE Not ready for Inspection IVRS - Inspection :*
NEED TO SEE YARDWATER PIPE SHADED W/CLEAN FILL
03/07/2007 PLUMBING - INTERMEDIATE Denied IVRS - Inspection :
See detailed listing on site.| 999*
TEST TUBS TO FLOOD LEVEL
SWEEPS REQUIRED ON TRAP ARMS
SUPPORT HORIZONTAL VENTS W/PIPE SUPPORTS
SEPARATE HOT & COLD WATER, USE PIPE CLAMPS
WATER SIZE NOT PER PLAN