Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 05/22/2007 | PLUMBING - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 05/17/2007 | PLUMBING - INTERMEDIATE | Partial Approval | IVRS - Inspection :* ABS TEST WAS NOT TO ROOF, POSSIBLE LEAK AT WEST WC WATER PIPING REDUCES FROM 1 1/2 TO 3/4, 3/4 THEN SUPPLIES ALL FIXTURES THIS DOES NOT APPEAR TO MEET PLANS ALSO, 3/4 IS SHOWN TO EACH FIXTURE 1 1/2 IS SHOWN TO WATER HEATER - IT IS NOT CLEAR WHAT SIZE IS COMING OUT OF WH AND IS NOT CLEAR HOW IT IS REDUCED. PROVIDE SCHEMATIC FOR CLARIFICATION OF SIZING. OK TO INSULATE ALL AREAS EXCEPT AT POSSIBLE LEAK AND AT WATER CHANGES. |
|
| 05/15/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* TEST TO BE THRU ROOF NO LEAKS ON TUBS WATER PIPING TO BE PER PLAN & SPEC |
|
| 05/14/2007 | PLUMBING - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* NEED TO SEE YARDWATER PIPE SHADED W/CLEAN FILL |
|
| 03/07/2007 | PLUMBING - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* TEST TUBS TO FLOOD LEVEL SWEEPS REQUIRED ON TRAP ARMS SUPPORT HORIZONTAL VENTS W/PIPE SUPPORTS SEPARATE HOT & COLD WATER, USE PIPE CLAMPS WATER SIZE NOT PER PLAN |