Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - FINAL
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 08/09/2007 | ELECTRIC - FINAL | Approved | IVRS - Inspection :* OK FINAL ALL UNITS |
|
| 08/07/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* UNIT #1 1. EXTERIOR GFI LOOSE 2. WASHER RECEPTACLE LOOSE 3. GROUND ALL SWITCHES 4. SECURE RANGE ANTI-TIP BRACKET TO FLOOR 5. BATH GFI COVER TO SEAT AGAINST WALL 6. DISPOSAL RECEPTACLE LOOSE 7. HAVE LOOSE RECEPTACLES THROUGHOUT GO THROUGH AND TIGHTEN AS NEEDED 8. STRAP AC FLEX UNIT #2 1. PANEL DIRECTORY NOT CORRECT 2. SECURE ANTI-TIP FOR RANGE FLOOR & BACK WALL 3. COVER PLATES TO SEAT AGAINST WALL 4. STRAP AC FLEX UNIT #4 1. BATH SWITCH LOOSE 2. STRAP AC FLEX THERE WILL BE A FEE IF ALL NOT CORRECT NEXT INSPECTION |
|
| 08/06/2007 | ELECTRIC - FINAL | Not ready for Inspection | IVRS - Inspection :* | |
| 08/02/2007 | ELECTRIC - FINAL | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR UNIT #3 ONLY GO THROUGH ALL UNITS PRIOR TO CALLING IN FINAL 1. AT AC'S STRAP FLEX WITHIN 12" OF TERMINATIONS 2. IDENTIFY WHITE USED AS HOT. ARE UNITS EQUIPPED WITH HEAT STRIPS? 3. ROOFTOP AND FRONT GFI NOT WORKING 4. INSTALL RANGE 5. PANEL DIRECTORY NOT CORRECT 6. PROVIDE DISCONNECTING MEANS FOR WATER HEATERS |