Inspection History Details
Inspection Status: Approved
Inspection History: ELECTRIC - INTERMEDIATE
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/27/2007 | ELECTRIC - INTERMEDIATE | Approved | IVRS - Inspection :* | |
| 04/16/2007 | ELECTRIC - INTERMEDIATE | Partial Approval | IVRS - Inspection :* 1. NEC 300.13B REQUIRES NEUTRAL ON 3 WIRE HOMERUNS TO BE PIGTAIL TO THE NEUTRAL IT FEEDS - THIS IS STILL NOT DONE AT UNIT #1 REFER, DISPOSAL 3 GANG -- CHECK THIS CORRECTION ALL UNITS 2. NEC 210.52 C1 REQUIRES THAT A COUNTER RECEPTACLE BE NO MORE THAN 24" FROM THE EDGE OF THE COUNTER OK TO ANOTHER RECEPTACLE IN THAT SPACE. IN UNIT #1, YOU HAVE OVER 48" ALONG BACK WALL LINE FROM RECEPTACLE TO RECEPTACLE. IN UNIT #2 THE RECEPTACLE IS MORE THAN 24" FROM EDGE OF COUNTER CHECK FOR PROPER LAYOUT OF ALL KITCHEN RECEPTACLES IN ALL UNITS. 3. NEC 314.16 REQUIRES THAT BOXES NOT BE OVERFILLED. THE AMOUNT OF CONDUCTORS ALLOWED IN THE BOXES IS STGAMPED IN THE BACK OF EACH BOX. THE GROUNDS ALL COUNT AS ONLY 1 CONDUCTOR. THE DEVICE (SWITCH OR RECEPTACLE) COUNTS AS TWO CONDUCTORS. ALL OTHER CONDUCTORS COUNT AS ONE EACH, IN UNIT #2 FOR THE LAUNDRY ARE LIGHT SWITCH BOX - IT IS STAMPED "10 #14" BUT YOU HAVE 11 #14'S CHECK ALL BOXES IN ALL UNITS TO MAKE SURE THEY ARE NOT OVERFILLED. OK COVER AFTER CORRECTION |
|
| 04/11/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : CORRECTIONS NOT FINISHED STILL NEED TO COMPLETE #2, #3, #4 FROM PREVIOUS INSPECTION. ALSO, SMOKE DETECTORS TO BE MINIMUM 36" HVAC SUPPLY OR RETURN OPENING WILL NEED TO PAY FEE IF NOT CORRECT NEXT INSPECTION. |
|
| 04/04/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : The wiring is not complete or does not comply with code.| 245* INSPECTION FOR UNIT 1 ONLY -- CHECK OTHERS 1. PANEL NOT ALLOWED IN BATHROOM -- NEC 240.24E 2. PIGTAIL NEUTRAL FOR ALL 3-WIRE HOMERUNS - NEC 300.13B 3. HAVE OVERFILLED BOXES - NEC 314.16 4. NEED KITCHEN COUNTER RECEPTACLES PROPERLY SPACED - NEC 210.52 5. PROPERLY SPACE WALL RECEPTACLES -- NEC 210.52 |
|
| 03/28/2007 | ELECTRIC - INTERMEDIATE | Not ready for Inspection | IVRS - Inspection :* | |
| 03/08/2007 | ELECTRIC - INTERMEDIATE | Denied | IVRS - Inspection : See detailed listing on site.| 999* INSPECTION FOR UNIT #1 ONLY -- CHECK THESE CORRECTIONS IN OTHER UNITS 1. WIRING NOT COMPLETE @ PANEL/HOME RUNS 2. USE PROPER CRIMP TOOL FOR CRIMP SLEEVES - NEC 110.3B 3. IDENTIFY WHITE USED AS HOT - NEC 200.6A 4. RANGE WIRING NOT IN 5. FINISH ALL BRANCH CKT WIRING AND MAKE UP 6. HAVE MISSING/NOT PROPERLY SPACED KITCHEN COUNTER RECEPTACLES - NEC 210.52 C1 7. FINISH ALL LOW VOLTAGE WIRING 8. PROPERLY SECURE/SUPPORT ALL ROMEX - NEC 334.30 PLEASE DO NOT CALL BEFORE READY OR A REINSPECTION FEE MAY BE CHARGED. |