Permit: T06BU01891

Parcel: 14029196A

Inspection Status: Approved

Inspection History: MODULAR - ELECTRIC INSPECTION

Date Description Inspector Results Comments
08/15/2006 MODULAR - ELECTRIC INSPECTION Approved IVRS - Inspection :*
08/14/2006 MODULAR - ELECTRIC INSPECTION Denied IVRS - Inspection :
See detailed listing on site.| 999*
SEE NOTES LAST INSP.
08/09/2006 MODULAR - ELECTRIC INSPECTION Denied IVRS - Inspection :
See detailed listing on site.| 999*
NOTES:
1. INSTALL 2" SEALTITE CONNECTOR PROPERLY AT SERVICE
2. ALUM, CONDUCTOR STRANDS CUT TO MAKE FIT IN LUGS AT SERVICE -- NOT APPROVED METHOD USE PROPER SIZED LUGS
3. SUPPORT FIRST POLE AT SERVICE -- LEANING TO FAR FEEDERS SPANNING OVER DRIVEWAY IS POTENTIAL HAZARD.