Microfiche records prior to 2006 have not been completely digitized and may not be available yet on PRO.
If you cannot find what you are looking for please
submit a records request.
Inspection Status: Violation
Inspection History: INITIAL CODE VIOLATION
| Date |
Description |
Inspector |
Results |
Comments |
| 01/03/2005 |
INITIAL CODE VIOLATION |
|
Violation |
NEON SIGN ON S TOWER FACE STARTED FIRE IN WOOD FRAME. EVIDENCE OF GRAND FAULT ARCING @ P K HOUSING AND AN IMPROPER HIGH VOLTAGE SPLICE BEHIND PK HOUSING. FURTHER EVIDNECE OF ELEC WORK ON SIGN (BRANCH CIRCUIT REPLACEMENT) WITHOUT PROPER PERMITS OR INSP. A DSD ELEC INSPECTOR WILL BE ASKED TO INVESTIGATE POSS WORK WOP. SIGN CIRCUIT LEFT OFF BLDG RETURNED TO MGT OF RESTUARANT. PERMITS REQUIRED TO REPLACE SIGN AND SHEATHING |