Case: T05VL00010
Case Details
Entered Date:
01/03/2005
Applicant:
RODRIGUEZ FAMILY FP LLC 51% &
Description:
COMPLAINT: EMER CALL OUT CFIR - NEON SIGN ON S TOWER FACE
Outstanding Inspections
Case Number: T05VL00010
Case Status: COMPLIAN
Case Description: COM: FIRE
Total Outstanding Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 01/03/2005 | INITIAL CODE VIOLATION | LHANLY | Violation | NEON SIGN ON S TOWER FACE STARTED FIRE IN WOOD FRAME. EVIDENCE OF GRAND FAULT ARCING @ P K HOUSING AND AN IMPROPER HIGH VOLTAGE SPLICE BEHIND PK HOUSING. FURTHER EVIDNECE OF ELEC WORK ON SIGN (BRANCH CIRCUIT REPLACEMENT) WITHOUT PROPER PERMITS OR INSP. A DSD ELEC INSPECTOR WILL BE ASKED TO INVESTIGATE POSS WORK WOP. SIGN CIRCUIT LEFT OFF BLDG RETURNED TO MGT OF RESTUARANT. PERMITS REQUIRED TO REPLACE SIGN AND SHEATHING |
Completed Inspections
Case Status: COMPLIAN
Case Number: T05VL00010
Case Description: COM: FIRE
Total Completed Inspections - 1
| End Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 04/21/2005 | FOLLOW UP CODE VIOLATION | RHOLLAND | Approved | OK TO CLOSE |