Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 03/28/2006 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 14 PSI TEST IS OK -- LEFT GAS CARD OK TO BACKFILL TRENCH CORRECTIONS HAVE BEEN MADE |
|
| 12/30/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999*SHALL PROVIDE THE REQUIRED TEST GAGE 15 LBS MAX WITH 1/10 INCREMENTS SHALL PROVIDE MIN OF 1" GAS SUPPLY TO EXISTING HOUSE CONNECTION. SHALL PROVIDE (2) 10 X10 LOUVER GRILLS LOCATED 12" BELOW CEILING AND 12" ABOVE FLOOR ON DOOR. SHALL PROVIDE A ROOF FLASHING ON ALL ROOF PENETRATIONS SHALL PROVIDE A AGA OR CSA GAS SHUT OFF VALVE @ WATER HTR LOCATED WITHIN 3" OF REGULATOR. SHALL PROVIDE WOOD BLOCKS WITH A 2 HOLE STRAPS FOR GAS LINE ON ROOF LOCATED EVERY 6' SHALL STRAP TO WALL GAS LINE EVERY 6' |