Permit: T05PL02097

Parcel: 11450001A

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
01/09/2006 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
1) GAS PRESSURE TEST IS OK
2) ALL CORRECTIONS HAVE BEEN MADE
3) NOTE: CONTRACTOR SHALL PERM CAP PROPERLY FLUE VENT WYE FOR WATER HTR CONNECTION TO FURNACE FLU VENT AND SEAL T & P DRAIN PENTRATION
01/08/2006 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*
01/06/2006 PLUMBING - GAS PRESSURE TEST Cancelled CANCELLED PER CONTRACTOR DAVID #245-9797
12/30/2005 PLUMBING - GAS PRESSURE TEST Denied IVRS - Inspection :
See detailed listing on site.| 999*SHALL PROVIDE THE REQUIRED TEST GAGE AND REQUIRED PRESSURE TEST 15 LBS MAX 1/10 INCREMENTS/ 3X THE WORKING PRESSURE
SHALL EXTEND FURNACE FLU VENT AND TERMINATE 2'-0" ABOVE COOLER WHEN FLU VENT IS LOCATED WITHIN 10' OF COOLER
SHALL EXTEND T & P DRAINS TO DAYLIGHT & REMOVE FLEX LINE
SHALL SECURE ALL GAS DROPS TO WALL
SHALL PROTECT ROMEX ELECTRICAL WIRE CONNECTION TO WATER HEATER.
SHALL CAP OFF WATER HTR FLU VENTS
12/27/2005 PLUMBING - GAS PRESSURE TEST Cancelled
12/27/2005 PLUMBING - GAS PRESSURE TEST Not ready for Inspection IVRS - Inspection :*