Permit: T05PL01928

Parcel: 125100310

Inspection Status: Approved

Inspection History: PLUMBING - GAS PRESSURE TEST

Date Description Inspector Results Comments
12/16/2005 PLUMBING - GAS PRESSURE TEST Approved IVRS - Inspection :*
12/01/2005 PLUMBING - GAS PRESSURE TEST Denied THIS INSPECTION IS FOR REPAIRS AND PARTIAL REPLACEMENT OF EXISTING GAS SYSTEMS/
ALL NEW PIPING TO BE AT LEAST 12" DEEP. GAS PIING MAY NOT LAY ON THE GROUND, BUT MUST BE KEPT AT LEAST 6" ABOVE GRADE/
ALL FITTINGS AND MARRED PIPE TO BE PRIMED AND TAPED
WHERE UNIONS ARE REQUIRED, RIGHT LEFT NIPPLES AND COUPLINGS SHALL BE USED.
VENT, TO VENT CONNECTOR NOT OK
NO BOND BETWEEN WATER AND GAS