Permit: T05PL01902

Parcel: 133250750


Addresses:

8642 E COLETTE ST

Inspection Status: Approved

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
12/01/2005 PLUMBING - FINAL Approved GAS PRESSURE TEST IS OK
ALL CORRECTIONS HAVE BEEN MADE
OK TO BACKFILL THE TRENCH
11/28/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*SHALL PROVIDE AN AIR PRESSURE TEST ON ENTIRE SYSTEM.
THERE IS A LEAK @ UNION @ HOUSE CONNECTION.
SHALL REMOVE THE FLEX LINE IN T & P DRAIN AND HARD PIPE.
THE T & P DRAIN FULL SIZE
SHALL REPLACE SHUT OFF VALVE @ GAS PACK ON ROOF
SHALL PROVIDE BONDING GROUND WIRE FOR GAS LINE # 6 WIRE MIN.
GAS LINE UNDER POOL DECK SHALL REQUIRE SLEEVE AND VENT
TAPE TRACER WIRE TO GAS LINE UNDER GROUND.