Inspection History Details
Inspection Status: Approved
Inspection History: PLUMBING - GAS PRESSURE TEST
| Date | Description | Inspector | Results | Comments |
|---|---|---|---|---|
| 11/07/2005 | PLUMBING - GAS PRESSURE TEST | Approved | IVRS - Inspection :* 1) 15 PSI TEST FROM METER TO WATER HEATER AND FURNACE 2) GAS CARD AT METER |
|
| 11/02/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : See detailed listing on site.| 999*14 PSI TEST ISNOT HOLDING PRESSURE PROVIDE A BOND JUMPER FROM ELEC. SERVICE TO GAS PIPE PROVIDE MIN. 3 SCREWS IN ALL JOINTS & CONNECTIONS ON VENT CONNECTORS TAPE IS NOT NECESSARY 1/4" I.D GAS FLEX TO FURNACE NOT ADEQUATE. USE A 3/8" ID FLEX |
|
| 11/01/2005 | PLUMBING - GAS PRESSURE TEST | Denied | IVRS - Inspection : There is no access to the site.| 920* |