Permit: T05PL01666

Parcel: 136284890


Addresses:

4432 S EVERGREEN AV

Inspection Status: Denied

Inspection History: PLUMBING - FINAL

Date Description Inspector Results Comments
10/18/2005 PLUMBING - FINAL Denied IVRS - Inspection :
See detailed listing on site.| 999*
1) PIPING CANNOT RUN IN RIGHT OF WAY. IT SHALL GO IMMEDIATELY ON TO PROPERTY
2) PIPING IS DAMAGED IN SEVERAL LOCATIONS
3) ALL PLASTIC GAS PIPING REQUIRES MINIMUM 18" COVER
4) WATER HEATER T & P DRIAN SHALL BE RIDGID PIPING GRAVITY DRAIN TO DAY LIGHT
5) PROVIDE 3-GALV SCREWS AT EACH JOINT OF WATER HEATER VENT PIPING
6) NO GAS PIPING SHALL BE UNDER GROUND UNDER A BLDG OR STRUCTURE
7) WHERE UNIONS ARE NECESSARY LEFT RIGHT NIPPLES AND COUPLINGS SHALL BE USED
8) PROVIDE BONDING OF BLDG GAS PIPING
9) VENT FROM WATER HEATER AND FURNACE WHEN WITHIN 10' OF COOLER INTAKE TO BE 3' WATER HEATER, 2' FURNACE ABOVE TOP OF COOLER INTAKE